System-sensor B200SR Manuel d'utilisateur

Naviguer en ligne ou télécharger Manuel d'utilisateur pour Équipement System-sensor B200SR. System Sensor B200SR User Manual Manuel d'utilisatio

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 4
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 0
SS-450-001 1 I56-3392-007R
B200SR
Intelligent Sounder Base
INSTALLATION AND MAINTENANCE INSTRUCTIONS
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
www.systemsensor.com
BEFORE INSTALLING
Please read the System Sensor Smoke Detector Application Guide, which pro-
vides detailed information on sensor spacing, placement, zoning, wiring, and
special applications. Copies of this manual are available from System Sensor.
NFPA 72 and NEMA guidelines should be observed.
NOTICE: This manual should be left with the owner/user of this equipment.
IMPORTANT: The detector used with this base must be tested and maintained
regularly following NFPA 72 requirements. The detector should be cleaned at
least once a year.
GENERAL DESCRIPTION
The B200SR sounder base is used with System Sensor 200-Series sensor heads
or equivalent. For a list of compatible sensors, refer to the System Sensor web-
site at www.systemsensor.com. Refer to the appropriate manual for more infor-
mation on sensors.
The B200SR sounder base was designed specifically to meet the needs of
dwelling unit applications. It offers maximum flexibility in configuration and
operation to meet or exceed the requirements of UL268 and UL464.
The sounder base is capable of producing either the distinctive three-pulse
temporal pattern (ANSI Temporal 3) fire alarm signal now required by NFPA
72 for commercial and residential applications or a continuous tone by simply
removing the included jumper from the device. Additionally, the B200SR is
designed to be compatible with existing installations of B501-Series sounder
bases.
The sounder base is intended for use with intelligent systems. The sounder
base requires an external 24 VDC power supply. The connections for the
external power supply and the communication loop are isolated to prevent
electrical interaction between them. Refer to the panel manual for maximum
allowable number of units per loop.
NOTE: For NFPA72 Installations, the Temporal 3 tone should be used for public
mode evacuation.
NOTE: When not used as a supplementary evacuation system, the external 24
VDC supply shall be treated as a component of the main power supply system
and shall fall under the requirements of the main power supply system per
NFPA 72.
Specifications
Base Diameter: 6.875” (17.46 cm)
Base Height (less sensor): 2.0” (5.08 cm)
Weight: 0.50 lb. (227 gm)
Operating Temperature Range: Refer to applicable sensor Operating Temperature Range using the Base/Sensor Cross Reference Chart at systemsensor.com
Operating Humidity Range: 10% to 93% relative humidity (non-condensing)
External Supply Electrical Ratings
External Supply Voltage: 16 to 33 VDC (VFWR)
Standby Current: 500 μA maximum
Alarm Current: 35 mA maximum
SLC Electrical Ratings
SLC Operating Voltage: 15 to 32 VDC
SLC Standby Current: 300 μA maximum
Sound Output Greater than 85 dBA minimum measured in a UL reverberant room at 10 feet, 24 Volts (in continuous tone)
WIRING GUIDELINES
All wiring must be installed in compliance with the National Electrical Code
and the local codes having jurisdiction and must not be of such length or wire
size which would cause the base to operate outside of its published specifica-
tions. The conductors used to connect smoke sensors to control panels and
accessory devices should be color coded to reduce the likelihood of wiring
errors. Improper connections can prevent a system from responding properly
in the event of a fire.
Wire sizes up to 12 AWG (2.5 mm
2
) may be used with the base. The sounder
base will be shipped with the screw terminals set for 14 AWG wiring. If 12
AWG wire is to be used, back out the screws to allow the wire to fit beneath
the clamping plates. For best system performance, the power (+ and -) wires
and the communication circuit wires should be twisted pair or shielded cable
installed in a separate grounded conduit to protect the communication loop
from electrical interference.
Make wire connections by stripping about 3/8” of insulation from the end of
the wire. Then, slide the bare end of the wire under the appropriate clamping
plate (See Figure 1), and tighten the clamping plate screw. Do NOT loop the
wire under the clamping plate (See Figure 2) The wiring diagram for a typical
2-wire intelligent system is shown in Figure 4.
CAUTION
For system monitoring - for terminals 4 and 5, do not use looped wire under termi-
nals. Break wire run as shown in Figure 2 to provide monitoring of connections.
I56-3392-007R
Vue de la page 0
1 2 3 4

Résumé du contenu

Page 1 - Intelligent Sounder Base

SS-450-001 1 I56-3392-007RB200SR Intelligent Sounder BaseINSTALLATION AND MAINTENANCE INSTRUCTIONS3825 Ohio Avenue, St. Charles, Illinois 601741-800-

Page 2 - Location of jumper–

SS-450-001 2 I56-3392-007RB200SR TERMINALSNo. Function1. Not Used2. Positive (+) Comm. Line In and Out3. Negative (-) Comm. Line In and Out4. Ext

Page 3 - C0970-10

(+) SLC(+) SLCNO 1NO 2NC 2COMM 2COMM 1NC 1(–) SLC(–) SLC(–) POWER(+) POWERU.L. LISTED COMPATIBLECONTROL PANELOPTIONAL SOUNDER INTERCONNECT*NOTUSEDSLC

Page 4 - ©2011 System Sensor

SS-450-001 4 I56-3392-007R ©2011 System SensorSystem Sensor warrants its enclosed smoke detector base to be free from defects in mate-rials and w

Commentaires sur ces manuels

Pas de commentaire