SS-450-005 1 I56-3739-001R
B210LP Plug-in Detector Base
INSTALLATION AND MAINTENANCE INSTRUCTIONS
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
www.systemsensor.com
BEFORE INSTALLING
Please read the System Smoke Detectors Application Guide, which provides
detailed information on detector spacing, placement, zoning, wiring, and spe-
cial applications. Copies of this application guide are available from System
Sensor. NFPA 72 guidelines should be observed.
NOTICE: This manual should be left with the owner/user of this equipment.
IMPORTANT: The detector used with this base must be tested and maintained
regularly following NFPA 72 requirements. The detector should be cleaned at
least once a year.
GENERAL DESCRIPTION
The B210LP is a plug-in detector base intended for use in an intelligent system,
with screw terminals provided for power (+ and –), and remote annunciator
connections. Communication takes place over the power (+ and –) lines.
BASE TERMINALS
NO. FUNCTION
1 Power (–), Remote Annunciator (–)
2 Power (+)
3 Remote Annunciator (+)
SPECIFICATIONS
Base Diameter: 6.1 inches (155 mm)
Base Height: .76 inches (19 mm)
Operating Temperature: Refer to applicable sensor Operating Temperature Range using the Base/Sensor Cross Reference Chart at systemsensor.com
Electrical Ratings:
Operating Voltage: 15 to 32 VDC
Standby Current: 170 µA
I56-3739-001R
SNAP ON
DECORATIVE
RING
SCREWS
(NOT SUPPLIED)
DETECTOR
BASE
BOX
(NOT SUPPLIED)
FIGURE 2. MOUNTING DETECTOR TO BOX:
C0128-06
TERMINAL 1
TERMINAL 2
TERMINAL 3
C0127-07
FIGURE 1. TERMINAL LAYOUT:
MOUNTING
This detector base mounts directly to 4-inch square (with and without plaster
rings), 4-inch octagon, 3
1
/2-inch octagon, and single gang junction boxes. To
mount, remove the decorative ring by turning it in either direction to unhook
the snaps, then separate the ring from the base. Install the base on the box
using the screws supplied with the junction box and the appropriate mounting
slots in the base.
Place the decorative ring on the base and rotate it in either direction until it
snaps into place (see Figure 2).
INSTALLATION AND WIRING GUIDELINES (SEE FIGURE 3)
All wiring must be installed in compliance with all applicable local codes
and any special requirements of the authority having jurisdiction. Proper wire
gauges should be used. The conductors used to connect smoke detectors to
control panels and accessory devices should be color-coded to reduce the like-
lihood of wiring errors. Improper connections can prevent a system from re-
sponding properly in the event of a fire.
For signal wiring (the wiring between interconnected detectors), it is recom-
mended that the wire be no smaller than 18 AWG (0.823 square mm). Wire
sizes up to 12 AWG (3.31 square mm) may be used with the base.
Make electrical connections by stripping about
3
/8 inch (10 mm) of insulation
from the end of the wire (use strip gauge molded in base). Then slide the wire
under the clamping plate and tighten the clamping plate screw. Do not loop
the wire under the clamping plate. (See Figure 4)
Check the zone wiring of all bases in the system before installing the detec-
tors. This includes checking the wiring for continuity, correct polarity, ground
fault testing and performing a dielectric test.
The base includes an area for recording the zone, address, and type of detec-
tor being installed. This information is useful for setting the detector head
address and for verification of the detector type required for that location.
Once all detector bases have been wired and mounted, and the loop wiring
has been checked, the detector heads may be installed in the bases.
Vue de la page 0
1 2

Résumé du contenu

Page 1 - B210LP Plug-in Detector Base

SS-450-005 1 I56-3739-001RB210LP Plug-in Detector BaseINSTALLATION AND MAINTENANCE INSTRUCTIONS 3825 Ohio Avenue, St. Charles, Illinois 601741-800-SE

Page 2 - BREAK TAB AT DOTTED LINE BY

FIGURE 5A. ENABLING THE TAMPER-RESISTANT CAPABILITY:PLASTIC LEVERBREAK TAB AT DOTTED LINE BY TWISTING TOWARD CENTER OF BASEUSE SMALL-BLADED SCREWDRIVE

Commentaires sur ces manuels

Pas de commentaire