System-sensor B401BH-2 Manuel d'utilisateur

Naviguer en ligne ou télécharger Manuel d'utilisateur pour Équipement System-sensor B401BH-2. System Sensor B401BH-2 User Manual Manuel d'utilisatio

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 2
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 0
D450-00-00 1 I56-2816-003R
B401BH-2
Sounder Bases
INSTALLATION AND MAINTENANCE INSTRUCTIONS
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
www.systemsensor.com
BEfORE INSTALLINg
Please thoroughly read the, System Smoke Detector Application Guide, which
provides detailed information on detector spacing, placement, zoning, wiring,
and special applications. Copies of this manual are available from System Sen-
sor. NFPA 72 and NEMA guidelines should be observed.
NOTICE: This manual should be left with the owner/user of this equipment.
IMPORTANT: The detector used with these bases must be tested and main-
tained regularly following NFPA 72 requirements. The detector used with
these bases should be cleaned at least once a year.
gENERAL DESCRIpTION
Model B401BH-2 sounder bases is intended for use with System Sensor 400
Series plug-in sensor heads in conventional 2-wire plug-in systems. Refer to
systems manuals for the maximum allowable number of units per loop. The
B401BH-2 requires an external 24VDC (nominal) supply with reverse polarity
capability. The connections of the external supply (terminals 1 and 2) and the
initiating loop (terminals 3, 4, and 5) are isolated in the B401BH-2 to prevent
electrical interaction between them.
A loop of horns can be made to sound by reversing the polarity of the external
supply.
NOTE: When the associated system is NOT used as a supplementary evacua-
tion system, the external 24VDC supply must be treated as a component of the
main power supply system with the result that it falls under the requirements
of NFPA 72.
B401BH-2 TERMINALS
No. Function
1 External Supply Positive (+)
2 External Supply Negative (–)
3 Negative (–) V
4 Positive (+) V In
5 Positive (+) V Out
Terminals 3, 4, and 5 are used for the communication/initiating circuit.
INSTALLATION WIRINg gUIDELINES
All wiring must be installed in compliance with the National Electrical Code
and all applicable local codes and any special requirements of the authority
having jurisdiction, using the proper wire size. The conductors used to con-
nect smoke detectors to control panels and accessory devices should be color-
coded to reduce the likelihood of wiring errors. Improper connections can
prevent a system from responding properly in the event of a fire.
SpECIfICATIONS
Base Diameter: 6 inches (152 mm)
Base Height (less base and sensor): 0.75 inches (19mm)
Weight: 0.32 lb. (145 g)
Operating Temperature Range: 14° to 140°F (–10° to +60°C)
Operating Humidity Range: 10% to 95%, non-condensing
Electrical Ratings
Voltage: 17 to 32 VDC
Standby Current: 1.0 mA maximum
Alarm Current: 15 mA maximum
Maximum Ripple Voltage: 10% of supply voltage
Start-up Capacitance: 200 µF
Horn Input Current Requirement: 600 µA maximum
Sound Output: Greater than 90 dBa measured in anechoic room at 10 feet (3 meters),
24 volts. 85 dBa minimum measured in UL reverberant room.
Sounder Delay Time: 0.75 to 5.7 sec
For signal wiring (the wiring between interconnected detectors), it is recom-
mended that the wire be no smaller than AWG 18. However, the screws and
clamping plate in the base can accommodate wire sizes up to AWG 12. The
use of twisted pair wiring or shielded cable for the power (+ and –) loop is
recommended to minimize the effects of electrical interference on the initiat-
ing loop.
Begin electrical connections by stripping about 3/8” insulation from the end
of the wire. Then, slide the bare end of the wire under the clamping plate and
tighten the clamping plate screw. Break the wire at each terminal to ensure
that the connections are supervised, as shown in Figure 2.
fIgURE 2.
DO NOT loop the wire under the clamping plate.
Check the zone wiring of the detector base before the detector heads are
installed. Perform continuity, base polarity, and dielectric tests on the wiring.
Smoke detectors and alarm system control panels have specifications for al-
lowable supervision current. Consult the control panel manufacturer’s speci-
fications for the total loop current supervision allowed for the control panel
being used before wiring the detector loops.
I56-2816-003R
fIgURE 1. TERMINAL LAyOUT :
C0471-00
C0473-00
Vue de la page 0
1 2

Résumé du contenu

Page 1 - Sounder Bases

D450-00-00 1 I56-2816-003RB401BH-2Sounder BasesINSTALLATION AND MAINTENANCE INSTRUCTIONS 3825 Ohio Avenue, St. Charles, Illinois 601741-800-SENSOR2,

Page 2 - DETECTOR

CLASS A OPTIONAL WIRINGUL LISTED COMPATIBLE CONVENTIONAL CONTROL PANELEXTERNAL 24V SUPPLYCLASS A OPTIONAL WIRINGULLISTED EOL RESISTORUL LISTED EOL REL

Commentaires sur ces manuels

Pas de commentaire