INSTALLATION AND MAINTENANCE INSTRUCTIONS
BEAM1224, BEAM1224S
Single-ended Reflected Type
Projected Beam Smoke Detector
3825 Ohio Avenue, St. Charles, Illinois 60174
800/736-7672, FAX: 630/377-6495
www.systemsensor.com
D400-73-00 1 I56-2294-006R
SPECIFICATIONS
GENERAL
Range: 16 to 230 Feet (5 to 70m); 230 to 328 Feet (70 to 100m) using optional accessory BEAMLRK
Sensitivity: 25% to 50% Total Obscuration in 6 levels
Level 1 = 25%
Level 2 = 30%
Level 3 = 40%
Level 4 = 50%
Level 5 = 30% to 50% (Acclimate)
Level 6 = 40% to 50% (Acclimate)
Spacing: 30 to 60 Feet (9.1 to 18.3m)
Response Time: ALARM - 20 seconds typical; TROUBLE - 30 seconds typical
Trouble Conditions: Beam Blockage (96% or More Obscuration)
Improper Initial Alignment
Self-compensation limit reached (service needed)
In Alignment mode
Test/Reset Features: Integral Sensitivity Test Filter (BEAM1224S only)
Sensitivity Filter (Incremental scale on reflector)
Local Alarm Test Switch
Local Alarm Reset Switch
Remote Test and Reset Switch Capability
Indicators: ALARM - Remote Output, Local LED (red)
TROUBLE - Remote Output, Local LED (yellow), Blink Pattern Indicates Trouble Diagnostics
NORMAL OPERATION - Local LED (flashing green once every 5 sec.)
ALIGNMENT AIDS - Optical Gunsight (coarse adjustment), 00 to 99 Digital Display (fine adjustment)
RELAYS - Alarm; Trouble
SENSITIVITY - Digital Display Readout in Percent Obscuration
ENVIRONMENTAL
Temperature: –22°F to 131°F (–30°C to 55°C); NOTE: For applications below 32°F (0°C), see Special Applications on page 2
Humidity: 10% to 93% RH Non-condensing
MECHANICAL
Shipping Weight: Complete unit: 3.9 lbs. (1.77 kg)
Shipping Size: 15˝×10.5˝×6.5˝ (381mm × 267mm × 165mm)
Mounting: Wall only without optional accessories
Wiring: Plug-in Terminal Blocks (12 to 22AWG)
Adjustment Angle: ±10° Horizontal and Vertical
Paintable Trim Ring: May be painted using enamel or acrylic type paints
ELECTRICAL
Voltage: 10.2 to 32 VDC (BEAM1224); 15 to 32 VDC (BEAM1224S)
Maximum Ripple Voltage: 6.0 volts (Peak-to-peak); NOTE: ripple must not fall below minimum operating voltage specification
Current (24 VDC): Avg. Standby - 17mA Max.
Avg. Alarm - 38.5mA Max.
Avg. Trouble - 8.5mA Max.
Avg. Alignment - 28mA Max.
Current (Test Mode, BEAM1224S only): Peak Test- 500mA Max.
Relay Contacts: 0.5A at 30 VDC
Reset Time: 0.3 Seconds Max.
Start-up Time (after 2 min. reset): 60 sec. Max.
Alarm Verification Time: 5 sec. Max.
Remote Output (Alarm & Trouble): VOLTAGE - 15 to 32 VDC; NOTE: Output voltage same as device input voltage
CURRENT - 15mA maximum; 6mA minimum; NOTE: Output current is limited by 2.2Kohm resistor
I56-2294-006R
BEFORE INSTALLING
Please thoroughly read this manual and applicable sections of System Sensor’s
Projected Beam Detector Application Guide. Copies of this manual are avail-
able from System Sensor.
GENERAL DESCRIPTION
System Sensor Model BEAM1224/BEAM1224S is a long range projected beam
smoke detector designed to provide open area protection. It is to be used
with UL-listed, separately supplied power (4-wire) control panels only. The
detector consists of a transmitter/receiver unit and a reflector. Smoke entering
the area between the transmitter/receiver and reflector causes a reduction in
signal. When the obscuration reaches alarm thresholds (chosen at the trans
-
mitter/receiver unit), the detector generates an alarm signal. Complete block-
age of the beam causes a trouble signal. Slow changes in obscuration due to
a build up of dirt or dust on the lens of the detector are compensated for by
Vue de la page 0
1 2 3 4 5 6 ... 12 13

Résumé du contenu

Page 1 - Projected Beam Smoke Detector

INSTALLATION AND MAINTENANCE INSTRUCTIONSBEAM1224, BEAM1224SSingle-ended Reflected Type Projected Beam Smoke Detector3825 Ohio Avenue, St. Charles, Ill

Page 2 - C1049-00

APPENDIX II. DETECTOR DRILLING TEMPLATE:4.345˝6.190˝ (157 mm) (110 mm)Scale = 1:1D400-73-00 10 I56-2294-006R

Page 3 - VERTICALLY FROM PEAK

D400-73-00 11 I56-2294-006R

Page 4 - REFLECTOR

APPENDIX III. REFLECTOR DRILLING TEMPLATE:Scale = 1:15.512˝(140mm)8.465˝(215mm)D400-73-00 12 I56-2294-006R

Page 5 - C0272-01

D400-73-00 13 I56-2294-006R ©2012 System SensorPlease refer to insert for the Limitations of Fire Alarm SystemsSystem Sensor warrants its enclose

Page 6 - C0264-01

D400-73-00 2 I56-2294-006Ra microcontroller that continuously monitors the signal strength and periodi-cally updates the alarm and trouble thresholds

Page 7 - C0268-00

DETECTOR PLACEMENTThis section of the manual discusses the placement of projected beam detec-tors. Though this information is based upon industry expe

Page 8 - OBSCURATION LEVEL

MOUNTING INSTRUCTIONSThe transmitter/receiver unit may be mounted over a recessed junction box. The cavity behind the detector is then used for routin

Page 9 - (BEAM1224)

FIGURE 7. WIRING CONNECTIONS AT DETECTOR:POWER OUT (–)POWER OUT (+)POWER IN (–)POWER IN (+)RESET I NPUTTEST INPUTAUX (–)REMOTE ALARM OUTNot usedREMOTE

Page 10 - (110 mm)

PRE-ALIGNMENT CHECKLIST• Ensure that both the detector and reflector are mounted securely to stable surfaces.• Ensure that all wiring is correct.•

Page 11 - D400-73-00 11 I56-2294-006R

D400-73-00 7 I56-2294-006RFIGURE 12. COARSE ALIGNMENT PROCEDURE:EYEREFLECTORC0265-00FIGURE 13. OUTER HOUSING SCREW LOCATIONS:SCREW LOCATIONSRESET SWI

Page 12 - Scale = 1:1

2. Place the blocking material over the reflector, lining it up with the gradu-ated marks that are 10 less than the detector’s setting in percent ob

Page 13 - ©2012 System Sensor

D400-73-00 9 I56-2294-006RAPPENDIX I. OPERATION MODES AND TROUBLESHOOTING GUIDE:Modes Red Yellow GreenDual Digital Display ReadoutInitiating MeansAla