INSTALLATION AND MAINTENANCE INSTRUCTIONS
BEAM200, BEAM200S
Single-ended Reflected Type
Projected Beam Smoke Detector
D400-74-00 1 I56-2289-005R
SPECIFICATIONS
GENERAL
Range: 16 to 230 Feet (5 to 70m); 230 to 328 Feet (70 to 100m) using optional accessory BEAMLRK
Sensitivity: 25% to 50% Total Obscuration in 6 levels
Level 1 = 25%
Level 2 = 30%
Level 3 = 40%
Level 4 = 50%
Level 5 = 30% to 50% (Acclimate)
Level 6 = 40% to 50% (Acclimate)
Spacing: 30 to 60 Feet (9.1 to 18.3m)
Response Time: ALARM - 20 seconds typical; TROUBLE - 30 seconds typical
Trouble Conditions: Beam Blockage (96% or More Obscuration)
Improper Initial Alignment
Self-compensation limit reached (service needed)
In Alignment mode
Test/Reset Features: Integral Sensitivity Test Filter (BEAM200S only, requires additional external power supply)
Sensitivity Filter (Incremental scale on reflector)
Local Alarm Test Switch
Local Alarm Reset Switch
Remote Test and Reset Switch Capability
Indicators: ALARM - Remote Output, Local LED (red)
TROUBLE - Remote Output, Local LED (yellow), Blink Pattern Indicates Trouble Diagnostics
NORMAL OPERATION - Local LED (flashing green with communication)
ALIGNMENT AIDS - Optical Gunsight (coarse adjustment), 00 to 99 Digital Display (fine adjustment)
SENSITIVITY - Digital Display Readout in Percent Obscuration
Style 7 Operation: On-board isolators provide style 7 operation,(may be disabled via shunts on circuit board)
ENVIRONMENTAL
Temperature: 22°F to 131°F (30°C to 55°C) NOTE: for applications below 32°F (0°C) see Special Applications section of this manual.
Humidity: 10% to 93% RH Non-condensing
MECHANICAL
Shipping Weight: Complete unit: 3.9 lbs. (1.77 kg)
Shipping Size: 15˝ × 10.5˝ × 6.5˝ (381mm × 267mm × 165mm)
Mounting: Wall only without optional accessories
Wiring: Plug-in Terminal Blocks (12 to 22AWG)
Adjustment Angle: ±10° Horizontal and Vertical
Paintable Trim Ring: May be painted using enamel or acrylic type paints
ELECTRICAL
Voltage: 15 to 32 VDC
Standby Current: Avg. Standby - 2mA Max. (1 communication every 5 sec., LED flashing, SLC @ 24 V)
Max. Alarm (LED on) - 8.5mA Max.
Max. Trouble (LED on) - 4.5mA Max.
Max. Alignment - 20mA Max.
External Supply (BEAM200S only): VOLTAGE - 15 to 32 VDC
CURRENT - 0.5A Max.
Remote Output (alarm): VOLTAGE - 15 to 32 VDC, NOTE: Output voltage same as device input voltage.
CURRENT - 15mA maximum, 6mA minimum; NOTE: Output current is limited by 2.2Kohm resistor
I56-2289-005R
3825 Ohio Avenue, St. Charles, Illinois 60174
1.800.SENSOR2; Fax: 630.377.6495
www.systemsensor.com
BEFORE INSTALLING
Please thoroughly read this manual and applicable sections of System Sensor’s
Projected Beam Detector Application Guide. Copies of this manual are avail-
able from System Sensor.
GENERAL DESCRIPTION
System Sensor Model BEAM200/BEAM200S is a long range projected beam
smoke detector designed to provide open area protection. It is to be used with
UL-listed compatible control panels only. The detector consists of a transmit-
ter/receiver unit and a reflector. When the obscuration reaches alarm thresh-
olds (chosen at the transmitter/receiver unit), the detector generates an alarm
signal. Complete blockage of the beam causes a trouble signal. Slow changes
in obscuration due to a build up of dirt or dust on the lens of the detector are
compensated for by a microcontroller that continuously monitors the signal
strength and periodically updates the alarm and trouble thresholds. When the
self-compensation circuit reaches its limit, the detector generates a trouble
signal, indicating the need for service.
Three LEDs on the detector indicate the current status: a red LED for alarm, a
yellow LED for trouble, and a blinking green LED for standby operation. Note:
The panel controls the status of the red and green LEDs. The local reset but-
ton is accessible by removing the outer paintable trim ring. The yellow LED
will blink in specific patterns to provide a diagnostic aid when diagnosing the
cause of a trouble signal. It will also blink the amount of drift compensation
that has been used at the conclusion of the test. Trouble signals automati-
cally reset upon removing the cause of trouble. Red and yellow LEDs can be
Vue de la page 0
1 2 3 4 5 6 ... 14 15

Résumé du contenu

Page 1 - Projected Beam Smoke Detector

INSTALLATION AND MAINTENANCE INSTRUCTIONSBEAM200, BEAM200SSingle-ended Reflected Type Projected Beam Smoke DetectorD400-74-00 1 I56-2289-005RSPECIFIC

Page 2 - C0306-01

D400-74-00 10 I56-2289-005RBlinks output by Yellow LED and Remote Trouble Outputonce the device has passed a local remote test:Percent The Detector

Page 3 - 12 IN. MIN

Scale = 1:1D400-74-00 11 I56-2289-005RAPPENDIX II. DETECTOR DRILLING TEMPLATE4.345˝6.190˝ (157 mm) (110 mm)

Page 4 - C0259-00

D400-74-00 12 I56-2289-005R

Page 5 - T3 T2 T1

APPENDIX III. REFLECTOR DRILLING TEMPLATEScale = 1:15.512˝(140mm)8.465˝(215mm)D400-74-00 13 I56-2289-005R

Page 6

D400-74-00 14 I56-2289-005R

Page 7 - C0266-00

D400-74-00 15 I56-2289-005R ©2009 System SensorSystem Sensor warrants its enclosed smoke detector to be free from defects in materials and workm

Page 8 - OBSCURATION LEVEL

D400-74-00 2 I56-2289-005Rremotely connected to the remote Alarm and Trouble outputs. These outputs mimic the functions of the detector’s red and ye

Page 9

Some fire codes specify spacing on a given center-to-center distance between detectors under ideal conditions. This spacing is based on rooms with smo

Page 10

the base. All four hole locations should be used to provide a secure mounting. The outer housing of the beam detector is held to the base using four s

Page 11 - (110 mm)

FIGURE 6. WIRING CONNECTIONS AT DETECTOR:SLC (–)SLC (+)SLC (–)SLC (+)RESET I NPUTTEST INPUTAUX (–)REMOTE ALARM OUTNOT USEDREMOTE TROUBLE OUTTEST OPTIO

Page 12 - D400-74-00 12 I56-2289-005R

STEP 1. COARSE ALIGNMENTRefer to Figures 11 and 12 for this step.1. Ensure that both of the optics lock-down screws are loosened so that the optics

Page 13 - Scale = 1:1

FIGURE 10. SWITCH LOCATIONS:ALIGNMENTSENSITIVITYTESTRESETSTYLE 7 ISOLATOR SHUNTS(SHOWN DISABLED)CODE SWITCH - TENS ONESC0263-00FIGURE 11. ALIGNME

Page 14 - D400-74-00 14 I56-2289-005R

Sensitivity SettingPercent ObscurationDisplay ReadingAcceptable Distance Between Detector & ReflectorFeet MetersLevel 1 25 25 16.4 to 120 5.0 to 3

Page 15 - ©2009 System Sensor

D400-74-00 9 I56-2289-005RIf the detector fails this test several steps should be taken to determine if the detector is faulty or simply needs to be