System-sensor IM-10 Manuel d'utilisateur

Naviguer en ligne ou télécharger Manuel d'utilisateur pour Équipement System-sensor IM-10. System Sensor IM-10 User Manual [en] Manuel d'utilisatio

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 4
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 0
Shipped on Board:
(1) Shunt in Class A/B position
(Shipped in Class B position, remove shunt for Class A)
COMPATIBILITY REQUIREMENTS
To ensure proper operation, this module shall be connected to a
listed compatible system control panel.
COMPONENTS
Following are descriptions of the IM-10 mounting frameworks.
There are two mounting options for IM-10 modules:
Up to six IM-10 modules can be installed on a CH-6 in a
BB-6 cabinet
One or two IM-10 modules can be installed in a BB-2 cabinet
Chassis
The CH-6 chassis is used to mount IM-10 modules in a BB-6 cabi-
net. It accommodates up to six IM-10 modules in a single cabinet
row three modules wide and two modules deep.
Figure 1. CH-6 Chassis:
The BB-2 cabinet has a built-in chassis that will accommodate
one or two IM-10 modules.
BEFORE INSTALLING
This information is included as a quick reference installation
guide. Refer to the appropriate control panel installation manual
for detailed system information. If the modules will be installed in
an existing operational system, inform the operator and local au-
thority that the system will be temporarily out of service. Discon-
nect the power to the control panel before installing the modules.
This system contains static sensitive components. Always ground
yourself with a proper wrist strap before handling any circuits so
that static charges are removed from the body. The housing cabi-
net should be metallic and suitably grounded.
NOTICE: This manual should be left with the owner/user of this
equipment.
GENERAL DESCRIPTION
The IM-10 Ten Input Monitor Module is intended for use in an in-
telligent alarm system. Each monitor module is intended to inter-
face between a control panel and normally open contact devices,
such as pull stations. A common SLC input is used for all mod-
ules, and the initiating device loops share a common supervisory
supply and ground. Otherwise, each monitor operates indepen-
dently from the others. Each module has its own unique address.
A pair of rotary code switches is used to set the address of the
first module from 01 to 90. The remaining modules are automati-
cally assigned to the next nine higher addresses. Provisions are
included for disabling a maximum of two unused modules to re-
lease the addresses to be used elsewhere. Each module also has
panel controlled green LED indicators. The panel can cause the
LEDs to blink, latch on, or latch off.
Included:
(6) 1 x 4 Terminal Blocks (2) 1
1
/4
(32mm) Stand offs
(4) Machine Screws (2) Nuts (3) Shunts (10) 47k Ohm
End of Line Resistors
D500-47-00 1 I56-1797-007
INSTALLATION AND MAINTENANCE INSTRUCTIONS
IM-10
Ten Input Monitor Module
SPECIFICATIONS
Normal Operating Voltage: 15–32 VDC
Stand-By Current: 3.5 mA
Alarm Current: 60 mA (assumes all ten LEDs solid on)
Temperature Range: 32°F to 120°F (0°C to 49°C)
Humidity: 10 to 93% Non-condensing
Dimensions: 6.8˝H x 5.8˝W x 1.25˝D
Accessories: CH-6 Chassis; BB-6 Cabinet; BB-2 Cabinet
Wire Gauge: 12-18 AWG
Maximum IDC Wiring Resistance: 40 Ohms
Maximum IDC Voltage: 12 VDC
Maximum IDC Current: 1 mA
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
www.systemsensor.com
C0202-00
C0206-00
I56-1797-007
Vue de la page 0
1 2 3 4

Résumé du contenu

Page 1 - Ten Input Monitor Module

Shipped on Board:(1) Shunt in Class A/B position (Shipped in Class B position, remove shunt for Class A)COMPATIBILITY REQUIREMENTSTo ensure proper

Page 2 - D500-47-00 2 I56-1797-007

3. Module Installation There are two methods for installing a module in the rear posi-tion of a chassis. Method one is for installation of a rear m

Page 3 - FCC Statement

D500-47-00 3 I56-1797-007Figure 6b. Installation of IM-10 module in front chas-sis position:231Step 1: Insert the bottom edge of the IM-10 module

Page 4 - C0886-01

0123456789BASE ADDRESSTO NEXTDEVICE–STATUSINDICATORS— +— +— +— +— +— +IDCADDRESS+0+1+2+3+4+5+6+7+8+9IDCADDRESSIDCADDRESSIDCADD