FIGURE 6. WIRING CONNECTIONS AT DETECTOR:
C0260-01
FIGURE 7. WIRING DIAGRAM:
+–
+–
+
+
TO NEX
T
DEVICE
FROM
PANEL OR
PREVIOUS
DEVICE
LISTED
REMOTE
POWER
SOURCE
ONLY USED FOR
BEAM200S. SEE
ELECTRICAL
RATINGS.
COMMUNICATION LINE
32 VDC MAX.
TWISTED PAIR IS
RECOMMENDED.
+
T3 T2 T1
C0261-00
FIGURE 8. WIRING DIAGRAM (RTS451 OR RTS151):
RTS451/KEY
or RTS151/KEY
DETECTOR
PIN 1
REMOTE ALARM OUT
T2-1
T2-2
T2-4
T2-3
AUX (–)
SLC IN +T1-1
T1-2
T1-3
T1-4SLC IN –
SLC OUT +
SLC OUT
RESET INPUT
TEST INPUT
T3-3
REMOTE TROUBLE OUTPUT
OPTIONAL YELLOW LED
PIN 2
PIN 4
PIN 3
PIN 5
C0328-03
FIGURE 9. WIRING DIAGRAM (RTS451 OR RTS151):
BEAM200/S
ALARM
SIGNAL
CIRCUIT
(NOTE 1)
T2-1
T2-2
NOTE 1: SEE ELECTRICAL RATINGS SECTION OF
THIS MANUAL FOR CIRCUIT OUTPUT RATINGS.
SLC (+)
SLC (–)
RED
C0320-00
INSTALLATION / ALIGNMENT
Reference Figures 10 through 14 for installation, alignment, and maintenance.
The alignment of the BEAM200/BEAM200S is divided into four steps: coarse
alignment, fine adjustment, final gain adjustment, and final verification. It is
necessary for all four steps to be executed properly to ensure proper alignment
of the product. If the detector and reflector are mounted per Mounting Loca-
tions and Mounting Instructions sections of this manual and the alignment
procedures are executed properly, false alarms and nuisance trouble signals
will be minimized.
PRE-ALIGNMENT CHECKLIST
Ensure that both the detector and reflector are mounted securely to •
stable surfaces.
Ensure that all wiring is correct.•
Ensure that terminal blocks are fully seated into their receptacles on •
the detector.
Complete any wiring dressing to minimize movement to the detector •
once the alignment procedure is completed.
Ensure that the appropriate number of reflectors are used for the in-•
stalled distance. Distances between 230 & 328 Feet (70 - 100m) require
additional reflectors (4 total). The BEAMLRK accessory should be used
in these cases.
Ensure that the line of sight between the detector and reflector is clear •
and that reflective objects are not too near. See Mounting Instructions
for more details.
Ensure that both the detector and reflector are mounted within their •
operational parameters for off axis angles. See Mounting Instructions
for more details.
Disable the zone or system to prevent unwanted alarms before applying •
power.
Ensure power to the detector is “ON”.•
Ensure that the appropriate address is set on the code wheels.•
You are now ready to begin the alignment procedure.