THRESHOLD TIME DELAY TRANSPORT TIMES
Day Alert: Calculated: Actual:
Action 1: Calculated: Actual:
Action 2: Calculated: Actual:
Fire 1: Calculated: Actual:
Fire 2:
Night Alert: Alarm outputs verified: Yes / No
Action 1: Fault outputs verified: Yes / No
Action 2: Isolate function verified: Yes / No
Fire 1: Transport time from each pipe
branch farthest hole verified:
Yes / No
Fire 2: Design calculations attached: Yes / No
Weekend Alert: Piping airtight and permanently affixed: Yes / No
Action 1: Piping labeled: Yes / No
Action 2: Detector activation(s) tested proper
desired operation at monitoring panel:
Yes / No
Fire 1: Detector trouble tested proper operation at
monitoring panel (airflow or filter removed):
Yes / No
Fire 2: Verified airflow through all holes: Yes / No
Acclimate Alert:
Action 1:
Action 2:
Fire 1:
Fire 2:
Air Flow Fault
Thresholds
Low:
High:
FAAST Device Validation Form (CONT.)
©2013 System Sensor. Product specifications subject to change without notice. ASFM16902 • 6/13
Comments:
systemsensor.com/faast