N770-03-00 1 I56-0394-010R
PIBV2 Post Indicator and
Butterfly Valve Supervisory Switch
INSTALLATION AND MAINTENANCE INSTRUCTIONS
IMPORTANT
Please Read Carefully and Save
This instruction manual contains important information on the installation
and operation of supervisory switches. Purchasers who install supervisory
switches for use by others must leave this manual or a copy of it with the
user. These instructions apply to System Sensor switches for post indicator
and butterfly type valves. Read all instructions carefully before beginning
installation.
CAUTION
Do NOT use this switch in explosive or potentially explosive atmospheres.
Do NOT leave unused wires exposed.
Before installing any supervisory switches in sprinkler systems, be thoroughly
familiar with:
NFPA 72: Installation, Maintenance and Use of Local Protective
Signalling Systems
NFPA 13: Installation of Sprinkler Systems, specifically Section 3.17
NFPA 25: Inspection, Testing and Maintenance of Sprinkler Systems, specifi-
cally Chapters 4 and 5
FIGURE 1:
COVER
TAMPER
SCREWS
TAMPER
PROOF
WRENCH
(P/N WFDW)
ACTUATING
CAM
ACTUATING
LEVER SCREW
NIPPLE SET SCREW
THREADED
NIPPLE
BASE HOUSING
ACTUATING
LEVER
RETAINING NUT
SWITCH ENCLOSURE
MOUNTING SCREWS
SPRING
HEX
WRENCH
(P/N HEXW)
4
1
/
4
˝ H
(ASSEMBLED)
3
1
/
4
˝ D
3
1
/
2
˝ W
W0224-00
SPECIFICATIONS
Contact Ratings: 10A @ 125/250 VAC ; 2.5 A @ 24 VDC
Dimensions: 4
1
4˝ H × 3
1
2˝ W × 3
1
4˝ D
Maximum Stem Extension: 3
5
32˝ (8.0 cm)
Operating Temperature Range: 32°F to 120°F (0°C to 49°C)
Shipping Weight 2 lbs.
Enclosure Rating: NEMA Type 3R when mounted with the actuator vertical (cover on top) as tested by Underwriters Laboratories, Inc.
IP54
U.S. Patent Number: 5,213,205
GENERAL INSTALLATION CONSIDERATIONS
1. Model PIBV2 is designed for installation in a
1
2˝ NPT tapped hole and
located so that the actuating lever of the switch engages the target or flag
of the valve . The switch actuating lever is spring loaded against the flag
or target of the valve and is released when the valve moves toward the
closed position from the fully open position. The switch is factory set to
indicate an alarm condition when the target and lever move in the direc-
tion toward the conduit entry hole when the valve closes, but can be
reversed if the installation demands (refer to Section 4).
2. Model PIBV2 is equipped with a removable
1
2˝ NPT pipe nipple which
is locked in place with one set screw. A hex wrench is provided for this
feature. The PIBV2 also includes an adjustable length actuating lever.
3. The cover is secured with two tamper resistant screws which require a
special key to remove. One key is included with each supervisory switch.
Replacement and additional keys are available (Part No. WFDW).
SECTION 1
INSTALLATION INSTRUCTIONS FOR POST INDICATOR VALVES
1. There are two types of post indicator valves – rising flag and falling flag.
In a rising flag installation, the PIBV2 mounts below the target assembly,
as shown in Figure 2A. Closing the valve raises the target assembly and
releases the actuating lever on the PIBV2. In a falling flag installation, the
PIBV2 mounts above the target assembly (Figure 2B). Closing the valve
lowers the target assembly and releases the actuating lever on the PIBV2.
The PIBV2 is set for falling flag installation. If a rising flag operation is
desired, it is necessary to reverse the action of the switch (See Section 4).
FIGURES 2A. RISING FLAG: FIGURE 2B. FALLING FLAG:
HEAD
TARGET
W0213-00
2. If the post indicator valve is predrilled with
1
2˝ NPT mounting hole,
remove the plug and go to step 6. If the post indicator valve is NOT
equipped with a
1
2˝ NPT mounting hole, it will be necessary to drill and
tap the hole.
3. Position the valve in the fully open position (“OPEN” should appear in
the window) and remove the head and target assembly. In doing so, en-
sure that the assembly can be reinstalled with its original adjustment.
N770-03-00 4 I56-0394-010R
©2008 System Sensor
System Sensor warrants its enclosed supervisory switch to be free from defects in materi-
als and workmanship under normal use and service for a period of three years from date
of manufacture. System Sensor makes no other express warranty for this supervisory
switch. No agent, representative, dealer, or employee of the Company has the authority to
increase or alter the obligations or limitations of this Warranty. The Company’s obligation
of this Warranty shall be limited to the repair or replacement of any part of the supervi-
sory switch which is found to be defective in materials or workmanship under normal
use and service during the three year period commencing with the date of manufacture.
After phoning System Sensor’s toll free number 800-SENSOR2 (736-7672) for a Return
Authorization number, send defective units postage prepaid to: System Sensor, Returns
1. Alarms generated by the activation of the actuating lever may not be received by a
central station if telephone or other communication lines to the alarm device are out
of service, disabled, or open.
WARNING
THE LIMITATIONS OF SUPERVISORY SWITCH ALARM DEVICES
2. Supervisory switch alarm devices have a normal service life of 10-15 years.
3. Supervisory switches are not a substitute for insurance. Building owners should
always insure property and lives being protected.
THREE-YEAR LIMITED WARRANTY
Department, RA #__________, 3825 Ohio Avenue, St. Charles, IL 60174. Please include a
note describing the malfunction and suspected cause of failure. The Company shall not
be obligated to repair or replace units which are found to be defective because of damage,
unreasonable use, modifications, or alterations occurring after the date of manufacture.
In no case shall the Company be liable for any consequential or incidental damages for
breach of this or any other Warranty, expressed or implied whatsoever, even if the loss
or damage is caused by the Company’s negligence or fault. Some states do not allow the
exclusion or limitation of incidental or consequential damages, so the above limitation
or exclusion may not apply to you. This Warranty gives you specific legal rights, and you
may also have other rights which vary from state to state.
I56-0394-010R
3825 Ohio Avenue, St. Charles, Illinois 60174
1.800.SENSOR2; Fax: 630.377.6495
www.systemsensor.com
Vue de la page 0
1 2

Résumé du contenu

Page 1 - PIBV2 Post Indicator and

N770-03-00 1 I56-0394-010RPIBV2 Post Indicator and Butterfly Valve Supervisory SwitchINSTALLATION AND MAINTENANCE INSTRUCTIONSIMPORTANTPlease Read Ca

Page 2 - W0223-00

N770-03-00 3 I56-0394-010RSECTION 4REVERSING THE ACTION OF PIBV21. Loosen the three 3/16˝ hex (socket head) screws on the top of the black switch

Commentaires sur ces manuels

Pas de commentaire