System-sensor PDRP-1001 Manuel d'utilisateur Page 15

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 56
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 14
Installing Optional Voltmeter/Ammeter 2. Installation
PDRP-1001 Instruction Manual PN 50734:D0 04/06/01
15
Installing Optional Voltmeter/Ammeter
To monitor battery voltage and battery charging current, a 4XMM Meter Module is required. To install
the power meter module follow the steps below:
The figure below shows the mounting location and connections for the Voltmeter/Ammeter.
Figure 3 Mounting and Connecting the Meters
Step Action
1
Cut the jumper wire labeled “AMP”.
2 Secure the module to the backbox with the hardware provided. Refer to
Product Installation Drawing (PID) for detailed instructions.
3
Connect meter cable P2 to connector J2 on the main circuit board.
4
Connect meter cable P3 to connector J3 on the main circuit board.
J3
J9
J2
AMP
TB5
0
10 20
30
DC VOLTS
3
DC AMPERES
0
3
MS44-mminst.cdr
‘AMP’ Jumper
Vue de la page 14
1 2 ... 10 11 12 13 14 15 16 17 18 19 20 ... 55 56

Commentaires sur ces manuels

Pas de commentaire