System-sensor HR-LF, HW-LF, P2RH-LF and P2WH-LF Manuel d'utilisateur Page 2

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 4
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 1
SS-120-006 2 I56-3889-000R
MOUNTING INDOOR WALL OR CEILING PRODUCTS
1. Attach mounting plate to junction box as shown in Figures 3 and 4. The
mounting plate is compatible with 4-inch square, double gang, and 4-inch oc-
tagon junction boxes (2-wire products may be used with a single gang box).
2. Connect field wiring to terminals, as shown in Figures 1 .
3. If the product is not to be installed at this point, use the paint cover to
prevent contamination of the mounting plate. (For indoor models only)
4. To attach product to mounting plate, remove the paint cover, then hook
tabs on the product housing into the grooves on mounting plate.
5. Then, swing product into position to engage the pins on the product with
the terminals on the mounting plate. Make sure that the tabs on the back
of the product housing fully engage with the mounting plate.
6. Secure product by tightening the single mounting screw in the front
of the product housing. For tamper resistance, the standard captivated
mounting screw may be replaced with the enclosed Torx screw.
SURFACE MOUNT BACK BOX MOUNTING
1. The surface mount back box may be secured directly to the wall or ceil-
ing. Grounding bracket provided if needed.
2. The wall mount box must be mounted with the up arrow pointing up.
3. Threaded knockout holes are provided for the sides of the box for ¾ inch
and ½ inch conduit adapter. Knockout plugs in the back of the box can
be used for ¾ inch and ½ inch rear entry.
4. To remove the ½ inch knockout, we recommend you use a flat head
screwdriver and place the blade along the inner edge and work your way
around the knockout as you strike the screwdriver, as shown in Figure
7. To remove the ¾ inch knockout place the blade of the screwdriver
along the edge and work your way around the knockout as you strike the
screwdriver, as shown in Figure 8.
5. V500 and V700 wiremold raceways are also provided. Use V500 for low
profile applications and V700 for high profile applications.
6. To remove the wire mold knockout turn pliers up, as shown in Figure 9.
7. Attach the mounting plate to the surface mount back box using the four
unpainted screws, as shown in Figure 5 or 6.
8. Follow steps 2-6 of the mounting indoor wall or ceiling products to wire
and attach the product.
+
+
INPUT
FROM
F
ACP
OR
PRIOR
DEVICE
OUTPUT
TO
NEXT
DEVICE
OR EOL
WIRING DIAGRAMS
FIGURE 1. WIRING 2-WIRE PRODUCTS:
A0367-01
SHORTING SPRING
A0368-00
SBB Shown
FIGURE 2. SHORTING SPRING:
2-wire mounting plate
Models are approved for Wall
and Ceiling installations.
A0453-00
A0454-00
FIGURE 3. WALL MOUNT LF SOUNDER:
FIGURE 4. WALL MOUNT LF SOUNDER/STROBE PRODUCT:
FIGURE 5. WALL MOUNT LF SOUNDER WITH
SURFACE MOUNT BACK BOX:
FIGURE 6. WALL MOUNT LF SOUNDER/STROBE
WITH SURFACE MOUNT BACK BOX
A0455-00
A0456-00
Vue de la page 1
1 2 3 4

Commentaires sur ces manuels

Pas de commentaire