TABLE 2. 2-WIRE LOW FREQUENCY SOUNDER/STROBE CURRENT DRAW (mA) FOR P2H-LF HIGH CANDELA RANGE SERIES:
Sound Pattern
16–33 Volts DC 16–33 Volts FWR
135 cd 150 cd 177 cd 185 cd 135 cd 150 cd 177 cd 185 cd
Temporal 277 292 325 344 296 309 343 351
Continuous 337 362 387 417 393 395 432 433
TABLE 3. LOW FREQUENCY SOUNDER OUTPUT (dBA) IN REVERBERANT (UL**) AND ANECHOIC ROOM:
Switch
Position
Sound Pattern
8–17.5 Volts** 16–33 Volts**
24 V Nominal Measurements
Reverberant Anechoic
DC FWR DC FWR DC FWR DC FWR
1 Temporal 76 76 76 76 76 76 86 86
2 Continuous 80 80 80 80 80 80 90 90
3* Coded 80 80 80 80 80 80 90 90
*Sounder ratings provided are for continuous voltage as provided by the NAC.
** Minimum dB rating for Operational Voltage Range as per UL 464.
SS-120-006 3 I56-3889-000R
A0459-00
A0460-00
A0461-00
CANDELA SELECTION
Adjust the slide switch on the rear of the product to position the desired can-
dela setting in the small window on the front of the unit. All products meet
the light output profiles specified in the appropriate UL Standards. Refer to
Figures 10-12.
SOUNDER SELECTION
Turn the rotary switch on the back of the product to the desired setting. For
sounder and sounder/strobe products (P2H-LF series), current draws are
listed in Tables 1 and 2. The sound output measurement for each sounder
setting is shown in Table 3.
FIGURE 9. V500 AND V700 WIRE MOLD REMOVAL FOR SURFACE
MOUNT BACK BOX
FIGURE 7. ½ INCH KNOCKOUT REMOVAL FOR SURFACE MOUNT
BACK BOX
FIGURE 8. ¾ INCH KNOCKOUT REMOVAL FOR SURFACE MOUNT
BACK BOX
TABLE 1. SOUNDER CURRENT DRAW (mA) FOR H-LF SERIES:
Position Sound Pattern
8–17.5 Volts 16–33 Volts
DC FWR DC FWR
1 Temporal 191 262 138 166
2 Continuous 292 384 138 208
3 Coded 292 388 153 205
NOTE: In position 3, temporal coding must be provided by the NAC. If the
NAC voltage is held constant, the sounder output will remain constantly on.
Coded ratings provided are for continuous voltage. Position 3 is not available
on 2-wire low frequency sounder/strobe products.